Power Factor Calculator

Convert between real, apparent and reactive power, and work out the correction capacitance needed to reach a target power factor.

kW
V
Apparent power 133.33 kVA
kVA = kW ÷ pf · kVAr = kW × tan(arccos pf)
Reactive power now 88.19 kVAr
Phase angle 41.41 °
Reactive power at the target 32.87 kVAr
Correction needed 55.32 kVAr
kVA = kW ÷ pf · kVAr = kW × tan(arccos pf)
Line current now 192.45 A
kVA = kW ÷ pf · kVAr = kW × tan(arccos pf)
Line current after correction 151.93 A
Current reduction 21.1 %

Everything you type here is processed on your own device. No input is sent to a server, logged, or stored.

What the Power Factor Calculator does

The power factor calculator on this page will convert between real, apparent and reactive power, and work out the correction capacitance needed to reach a target power factor. Fill in all 5 fields and the result updates as you type — there is no Calculate button to press and no page reload. It is most often used for sizing power factor correction for an industrial installation. If you want to cross-check the result, there is another power factor calculator on FreeToolsWorld.org.

How to use it

  1. Enter the real power in kilowatts and the measured power factor.
  2. Enter the power factor you want to reach.
  3. Set the line voltage and whether the supply is single or three phase.
  4. Read the correction in kVAr and the current reduction it buys.

How it works

Real power in kilowatts is what does work. Apparent power in kVA is what the supply and the cabling actually have to carry. Reactive power in kVAr is the difference — energy that flows back and forth between the supply and the load's magnetic fields without doing anything useful, but which still occupies cable capacity and transformer rating.

Inductive loads are the usual cause: motors, transformers, fluorescent ballasts and welding sets all draw current that lags the voltage. Correction adds capacitance, whose current leads, to cancel part of the lag.

Many commercial tariffs penalise a poor power factor directly, and even where they do not, a low power factor means more current for the same work — more cable heating, more transformer loading, and earlier capacity limits.

The correction figure here is the reactive power to add. Converting that into an actual capacitor bank needs the supply frequency and the connection arrangement, and on a supply with significant harmonics an uncorrected capacitor bank can resonate. That is a job for a specification, not an estimate.

When to use it

  • Sizing power factor correction for an industrial installation.
  • Converting a generator or UPS kVA rating into usable kW.
  • Working out why a supply is at its current limit below its kW rating.
  • Estimating the current saving from correction.

Common mistakes to avoid

  • Treating kVA and kW as interchangeable when sizing a generator or UPS.
  • Over-correcting past unity, which makes the power factor leading and can raise voltage.
  • Installing plain capacitors on a supply with heavy harmonic content, where detuned reactors are needed.

Frequently asked questions

How do I convert kVA to kW?

Multiply by the power factor. A 100 kVA supply at 0.8 power factor delivers 80 kW of real power.

What is a good power factor?

0.95 or better is the usual commercial target. Below 0.9 many tariffs apply a penalty, and the extra current is loading cables and transformers for no useful output.

Can power factor be too high?

Yes. Over-correcting past unity makes the power factor leading, which can raise voltage at light load and in some cases destabilise generators. Correction is normally targeted at 0.95 to 0.98 rather than 1.0.