Wire Size Calculator

Calculate the resistance and voltage drop of a cable run from its cross-section, length and current, in copper or aluminium.

mm²
m
A
V
°C
Resistivity at that temperature 0.0000000172 Ω·m
Resistance one way 0.13792 Ω
Resistance there and back 0.27584 Ω
R = ρL/A · Vdrop = I × 2R (there and back)
Voltage drop 4.413 V
R = ρL/A · Vdrop = I × 2R (there and back)
Drop as a share of supply 1.92 %
R = ρL/A · Vdrop = I × 2R (there and back)
Power lost as heat in the cable 70.62 W
Against the common 3% guideline Within 3%

Everything you type here is processed on your own device. No input is sent to a server, logged, or stored.

What the Wire Size Calculator does

Use this wire size calculator to calculate the resistance and voltage drop of a cable run from its cross-section, length and current, in copper or aluminium. Fill in all 6 fields and the result updates as you type — there is no Calculate button to press and no page reload. It is most often used for checking whether a long run will drop too much voltage. For a second version of this wire size calculator, see FreeToolStation.org.

How to use it

  1. Enter the conductor cross-section in square millimetres.
  2. Enter the one-way length of the run — the tool doubles it for the return path.
  3. Enter the current the circuit will carry and the supply voltage.
  4. Pick copper or aluminium and set the expected conductor temperature.

How it works

The loop resistance is what matters, not the one-way figure: current flows out along one conductor and back along the other, so a 20 metre run is 40 metres of conductor. Calculators that forget the return path understate the drop by half.

Copper resistivity rises about 0.393% per degree Celsius. A cable running warm in a conduit on a hot day can be 30 to 40 degrees above the 20 °C reference, which adds 12 to 16% to its resistance and to the voltage drop.

This calculates voltage drop only. It is not a current-carrying-capacity calculation and it is not a substitute for the wiring regulations that apply where you are: ampacity depends on insulation type, grouping, ambient temperature, installation method and protective device, none of which are inputs here. Treat this as a sizing estimate and check it against the applicable standard before installing anything.

When to use it

  • Checking whether a long run will drop too much voltage.
  • Sizing cable for a low-voltage DC system, where drop matters most.
  • Estimating the heat a cable run will produce.
  • Comparing copper against aluminium for a given run.

Common mistakes to avoid

  • Using one-way length instead of the loop.
  • Calculating at 20 °C for a cable that will run at 60.
  • Treating a voltage-drop result as a verdict on whether the cable is safe. Ampacity is a separate question governed by regulation.

Frequently asked questions

What is an acceptable voltage drop?

Three percent for a final circuit is the figure most often cited, with five percent total from the supply origin. The binding number is whatever your local wiring regulations specify.

Why does voltage drop matter more on low-voltage systems?

Because the percentage is what counts. A 1 V drop is 0.4% of 230 V and 8% of 12 V. Low-voltage DC runs need disproportionately thick cable for the same power.

Does this tell me what cable is safe to use?

No. It calculates voltage drop only. Current-carrying capacity depends on installation method, grouping, ambient temperature and insulation, and is governed by the wiring regulations that apply where you are.