Generator Fuel Consumption Calculator
Estimate how much fuel a generator burns per hour at a given load, how long a tank lasts and what the running cost is, for diesel, petrol or propane.
Everything you type here is processed on your own device. No input is sent to a server, logged, or stored.
What the Generator Fuel Consumption Calculator does
This generator fuel consumption calculator will estimate how much fuel a generator burns per hour at a given load, how long a tank lasts and what the running cost is, for diesel, petrol or propane. Fill in all 7 fields and the result updates as you type — there is no Calculate button to press and no page reload. It is most often used for estimating how much fuel to have on site for a planned outage. A related tool on this site is the spring rate calculator.
How to use it
- Enter the actual load in kilowatts — not the generator rating.
- Enter the nameplate rating and power factor so the load percentage can be shown.
- Pick the fuel, or enter your own specific consumption if the datasheet gives one.
- Add tank size and fuel price for runtime and running cost.
How it works
Fuel consumption scales with the load, not with the size of the generator. A diesel set burning 0.27 litres per kilowatt-hour under an 8 kW load uses 2.16 litres an hour, whatever its rating — a 20 kVA set and a 60 kVA set carrying the same 8 kW burn roughly the same fuel, with the larger one somewhat worse because it is running lighter. On a 50 litre tank that 2.16 L/h gives 23.1 hours, and at 1.55 a litre it costs 3.35 an hour.
The load percentage is why the rating still matters. Fuel curves are published against percentage of rating, and specific consumption is not flat: it is poor below about 30% load, best somewhere between 70% and 85%, and rises again at full load. An 8 kW load at 0.8 power factor is 10 kVA, which is 50% of a 20 kVA set — comfortable territory. The same load on a 60 kVA set is 17%, where a diesel engine runs cold, burns fuel incompletely and wet-stacks: unburnt fuel and soot glaze the bores and foul the turbo and exhaust. Generator hire firms care about this more than fuel cost, because light running is what wrecks engines.
Power factor is the bridge between the kilowatts your equipment draws and the kilovolt-amperes the generator is rated in. Nameplates are almost always at 0.8, so a 20 kVA set is a 16 kW set. Resistive loads — heaters, filament lighting, kettles — run at a power factor near 1, while motors and older switch-mode supplies pull it down. Sizing a generator from kVA and then loading it to that figure in kilowatts overloads it by 25%.
Starting surge is the sizing trap this calculation does not show. An induction motor draws several times its running current for the first second or two, so a 3 kW compressor can momentarily demand 15 kW or more. That is why generator sizing is done on starting load rather than running load, and why a set that looks comfortably loaded on paper trips when the air conditioning cuts in. Above 80% running load there is no room for it.
Fuel type changes the number substantially. Diesel is the most energy-dense of the three at around 0.27 L/kWh for a reasonably loaded set; petrol is roughly 0.33 because the fuel has less energy per litre and spark ignition is less efficient; propane is about 0.42 by liquid volume for the same reason again, though it stores indefinitely and runs cleaner. Cost per kilowatt-hour generated — the last row here — is usually several times grid electricity, which is the figure to look at before running a generator for anything other than an outage.
When to use it
- Estimating how much fuel to have on site for a planned outage.
- Working out whether a tank will last overnight without refuelling.
- Checking the running cost per kilowatt-hour against grid electricity.
- Seeing whether a generator is being run at a sensible load percentage.
- Comparing diesel, petrol and propane running costs for the same load.
Common mistakes to avoid
- Calculating consumption from the generator rating instead of the actual load.
- Loading a generator to its kVA figure in kilowatts. At a 0.8 power factor that is a 25% overload.
- Running a diesel set at under 30% load for long periods, which causes wet-stacking.
- Sizing on running load and ignoring motor starting surge, which can be several times higher.
- Treating specific fuel consumption as constant. It is noticeably worse at light load.
Frequently asked questions
How much fuel does a generator use per hour?
Roughly the load in kilowatts multiplied by the specific fuel consumption — about 0.27 L/kWh for diesel at a sensible load. An 8 kW load therefore burns around 2.16 litres an hour. Light loading makes it worse, sometimes substantially.
What load percentage should I run a generator at?
Between about 50% and 80% of rating is the sweet spot: efficient, and with headroom for starting surges. Below 30% a diesel engine runs too cold and wet-stacks; above 80% there is no margin for a motor start.
What is wet-stacking?
Unburnt fuel passing through an under-loaded diesel engine, where it glazes the cylinder bores and fouls the turbocharger and exhaust. It is caused by extended light-load running, and the fix is to load the set properly or fit a load bank.
Why is the kVA rating higher than the kW rating?
Because the nameplate assumes a power factor, almost always 0.8. A 20 kVA generator delivers 16 kW of real power at that power factor. Loading it to 20 kW would be a 25% overload.
Is running a generator cheaper than grid electricity?
Almost never. The cost per kilowatt-hour generated here is typically several times a domestic electricity tariff once fuel is counted, before servicing and oil changes. Generators are for outages and places without a supply, not for saving money.