Air Changes Per Hour Calculator
Work out air changes per hour from a room volume and a fan flow rate, or the flow rate needed to reach a target ACH.
Everything you type here is processed on your own device. No input is sent to a server, logged, or stored.
What the Air Changes Per Hour Calculator does
Use this air changes per hour calculator to work out air changes per hour from a room volume and a fan flow rate, or the flow rate needed to reach a target ACH. Fill in all 7 fields and the result updates as you type — there is no Calculate button to press and no page reload. It is most often used for sizing an extract fan for a bathroom or kitchen. Companion tools to this one live on FreeToolStation.org.
How to use it
- Enter the room dimensions.
- Enter the fan or system flow rate and its unit.
- Set a target ACH to see the flow you would need.
- Allow for duct losses — a fan rarely delivers its rated flow in situ.
How it works
Air changes per hour is the simplest ventilation measure there is: the volume of air supplied in an hour divided by the volume of the room. Six ACH means the room’s full volume of air is replaced six times an hour, or once every ten minutes. The arithmetic is trivial; the two interesting parts are what the target should be and why the real figure is usually below the calculated one.
Targets vary by what the room is for, because ventilation is removing something specific. A bedroom needs 1 to 2 ACH, mainly to deal with moisture and carbon dioxide from breathing. A bathroom needs 6 to 8 because of water vapour. A kitchen needs 7 to 15 for moisture, grease and cooking odours, and a commercial kitchen 15 to 30. A laboratory or a workshop handling solvents needs 6 to 12 or considerably more, set by the substance rather than by comfort. These are starting points: the number that actually applies comes from the local building code or the relevant standard for the occupancy.
The honest caveat about ACH as a measure is that it assumes perfect mixing, and rooms do not mix perfectly. If the inlet and the extract are close together, air short-circuits between them and a substantial part of the room never sees fresh air regardless of what the headline figure says. That is why inlet and extract placement matters as much as fan size — diagonally opposite, with the extract where the contaminant is generated, does far more than a bigger fan in the wrong place.
The other systematic gap is between a fan’s rated flow and its delivered flow. Manufacturers measure flow against free air with no resistance. In a real installation the fan is on the end of several metres of duct, with bends, a grille and possibly a backdraught shutter, and each of those costs pressure. Delivered flow is frequently 30 to 50 per cent below the rating, with flexible ducting and tight bends the worst offenders. Sizing a fan to exactly the calculated requirement reliably under-ventilates; sizing with headroom, and using smooth rigid duct with gentle bends, is what gets the design figure in practice.
For occupied spaces, a per-person check is often more relevant than ACH. Guidance for offices and classrooms is commonly around 8 to 10 litres per second per person, which in a crowded room can demand considerably more air than an ACH target would suggest. Where people are the main source of what you are ventilating, the per-person figure is the one that binds.
When to use it
- Sizing an extract fan for a bathroom or kitchen.
- Checking whether existing ventilation meets a target.
- Converting between cfm, litres per second and cubic metres per hour.
- Working out ventilation per person for an office or classroom.
- Checking a workshop against a contaminant-removal requirement.
Common mistakes to avoid
- Sizing a fan to exactly the calculated flow with no allowance for duct losses.
- Placing inlet and extract close together, so air short-circuits and part of the room is unventilated.
- Using a bathroom target for a kitchen, or a comfort target where a contaminant sets the requirement.
- Using flexible ducting with tight bends, which can halve the delivered flow.
- Relying on ACH alone in a crowded room, where the per-person figure binds first.
Frequently asked questions
How do I calculate air changes per hour?
Divide the flow rate in cubic metres per hour by the room volume in cubic metres. A 48 m³ room with 320 m³/h of flow gets 6.67 air changes an hour.
How many air changes per hour do I need?
It depends on the room: roughly 1 to 2 for a bedroom, 6 to 8 for a bathroom, 7 to 15 for a kitchen, 2 to 6 for an office, 15 to 30 for a commercial kitchen. Your local building code or the relevant standard sets what actually applies.
How do I convert cfm to air changes per hour?
Multiply cfm by 1.699 to get cubic metres per hour, then divide by the room volume in cubic metres. Or work in imperial throughout: cfm × 60 ÷ room volume in cubic feet.
Why does my fan not achieve its rated flow?
Because the rating is measured against no resistance. Ducting, bends, grilles and shutters all cost pressure, and delivered flow is commonly 30 to 50 per cent below the rating. Flexible duct with tight bends is the worst case.
Is ACH a reliable measure of ventilation?
It is a useful one that assumes perfect mixing. If the inlet and extract are close together, air short-circuits and part of the room stays unventilated whatever the ACH figure says. Placement matters as much as flow.